180 ■ Fandis TCU 200 AC 200W Thermoelectric units AC air-air General specifications • Panel through mounting, see mounting cut-out. Fixing with M5 ISO screws (not supplied). Suitable for any plate thickness • Stainless steel external cover • Sealing gasket made of closed cell polyethylene foam • Shielded and self-lubricating ball bearing fans • Terminal block connection f f AC/DC power supply integrated f f No chlorofluorocarbons (CFC) f f Precise temperature control f f Operation in any orientation f f Long life f f Not sensitive to vibration f f No moving parts except the fans Technical data Model Cooling Power Rated VoltageRange Input Power Max Input Power Operating Temp. Range Weight Approvals W V W W °C Kg TCU200AC40-SIP 201 88-264 Va.c. 245 306 -20 ~ +50 16.61 CE; Technical drawing Mounting cut-out Cabinet wall Cold side Warm side 290 347 224.3 99.8 124.5 312.5 276 160±0.5 N ° 8 HOLES Ø 5.5 291±0.5 +1 -0 291 305±0.5 +1 - 0 276 140±0.5 ∆T = Te - Ti [°C] Cooling Power [W] 0 20 40 60 80 100 120 140 160 180 200 220 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 Te = 25 °C Q c = - 6.5797 ∆T + 201.09